Type
Flame-retardant rubber sheathed cable
I. Application
This product is a series of rubber sheathed soft cables for mining. It is suitable for power connection of coal mining machines and similar equipment with rated voltage Uo/U of 1.9/3.3KV and below. It is mostly used in coal mines.
II. Use conditions
The long-term allowable working temperature of the wire core is 65℃, and the minimum bending radius of the wire is 6 times the cable diameter. Yellow sheathed cables must not be exposed to sunlight for a long time.
Nuclear grade cable
Scope of application
·This product is suitable for control and signal connection cables used in control system networks with rated voltage Uo/U of 0.6/1kV in nuclear power plants.
·The long-term allowable working temperature of the cable conductor is 90℃, and the maximum temperature of the cable conductor during short circuit shall not exceed 250℃, and the duration shall not exceed 5 seconds.
·The ambient temperature when laying cables should not be lower than 0℃.
·The allowable bending radius during cable laying is:
- For cables without armor, it should be no less than 6 times the cable diameter
- For cables with armor or copper tape shielding, it should be no less than 12 times the cable diameter
- For flexible cables with shielding structure, it should be no less than 6 times the cable diameter.
·When the long-term allowable operating temperature of the conductor is not more than 90℃, the identification life of the cable shall be no less than 40 years.
·The finished cable shall comply with the requirements of the Class A bundled combustion test specified in the GB/T18380.3 standard.
·Smoke density of finished cable: light transmittance is not less than 70%.
·Radiation resistance: 25×104Gy
·Halogen-free: When non-metallic materials are burned, the acidity of the escaping gas (expressed as pH value) should be greater than 4.3; the conductivity should not be greater than 10μS/mm.